All of Gibson Stainless’ products are designed to meet and exceed industry and UL standards. Gibson Stainless is constantly working to improve its product line. The following product lines are UL Listed and others may be pending UL approval.

For more information on UL Certifications, click here.

Currently, our GUA series hazardous-location conduit bodies carry a Type 4X rating.

NEMA Type ratings are applied to electrical enclosures, as summarized in this NEMA document. The purpose of the Type ratings is to provide a characterization of an enclosure’s ability to protect personnel from the contents of the enclosure and to protect the equipment in the enclosure from the environment outside, as well as to ensure overall quality of the part. Fittings intended to be installed with an enclosure may also carry a NEMA Type rating to indicate that the assembly will provide at least an equivalent level of protection as the standalone enclosure. The fitting rating is required to be equal to or greater than the rating applied to the enclosure to maintain an overall rating equal to the enclosure rating.

In the spirit of the rating, our conduit and our fittings do prevent ingress of large, solid foreign objects into the raceway and will perform, undamaged, should ice form externally on the raceway. Our conduit and some of our fittings, like other standard, rigid conduit systems, are not designed to be completely watertight and may or may not prevent the ingress of water.

NEMA establishes ratings for enclosures in NEMA 250; these ratings can be self-deducted by the manufacturer. All of Gibson Stainless’ products are designed to meet and exceed industry standards, and Gibson Stainless is constantly working to improve its product line. At any given time, other product lines may be undergoing testing to determine NEMA type rating. Contact the manufacturer for additional information.

For more information on NEMA ratings, click here.

Enclosures are assigned an IP (International Protection) Code to signify the degree of protection they provide against ingress of solid foreign objects and water and against access to dangerous parts inside the enclosure. International Electrotechnical Commission (IEC) standard 60529 contains the guidance for assigning an IP Code to an enclosure, which consists of the letters “IP” followed by two numerals: The first numeral indicates the degree of protection provided to persons against access to hazardous parts inside the enclosure and the degree of protection against ingress of solid foreign objects, while the second numeral indicates the degree of protection against harmful ingress of water. IP ratings, and IEC standards in general, are typically applied to products with a significant presence in the European market; as such, Gibson Stainless products do not carry IP ratings.

For more information on IP ratings, click here.

Gibson Stainless’ conduit is manufactured in accordance with and certified to ANSI/UL 6A-2014, which is the Standard for Safety for Electrical Rigid Metal Conduit – Aluminum, Red Brass, and Stainless Steel. Based on the scope of ANSI C80.1-2015, this standard is intended for use with conduit employing a metallic zinc coating or alternate corrosion protection coating; therefore, it does not apply to Gibson Stainless’ conduit. ANSI/UL 6A-2014 would be the parallel standard for stainless steel conduit that does not need to employ any type of corrosion protection coating.

Stainless steel: -50 °F (-45 °C) to 1700 °F (925 °C)
– For optimum corrosion resistance, limit temperatures to 800°F (425°C)
– For intermittent service, limit temperatures to 1600°F (870°C); despite the reduced time at temperature inherent in intermittent service, the upper end of the range is suppressed as a result of the thermal cycling and resultant fatigue in an environment where service temperatures are changing.

Low Temperature Performance:
Austenitic stainless steels (e.g., 304SS and 316SS) have a face-centered cubic crystalline structure, which prevents them from undergoing a ductile-to-brittle transition like metals with a body-centered cubic crystalline structure. This means that austenitic stainless steels have good low temperature properties, even permitting use at cryogenic temperatures.

High Temperature Performance:
Austenitic stainless steels (e.g., 304SS and 316SS) maintain their atomic structure at high temperatures giving them great value as structural materials. Ordinary carbon steel undergoes a phase change around 1400 °F (760 °C) that results in rapid shrinkage, which can cause catastrophic structural failure in structural elements already weakened by heat. Testing on fiberglass, aluminum, galvanized steel and stainless steel structural members under load and exposed to temperatures from 430°F (220°C) to in excess of 1050°F (565°C) demonstrate significant degradation to complete failure of the alternate structural materials while stainless steel remains intact.

At temperatures above 800°F (425°C), sensitization, or carbide precipitation, can occur reducing the overall corrosion resistance of the product. If service temperatures in this range are anticipated, low-carbon variants of the stainless steel alloy should be specified by the purchaser. The manufacturer should be contacted for additional information.

Rubber and Plastic:
Products containing chloroprene/neoprene gaskets, BUNA-N/nitrile O-ring, and polypropylene seals (liquidtight fittings):
-20 °F (-29 °C) to 190 °F (88 °C)
Products containing Polyetherimide (PEI) Thermoplastic (insulated, grounding bushings):
-40 °F (-40 °C) to 302 °F (150 °C)

Standard:
-22°F (-30°C) to 176°F (80°C) Dry /140°F (60°C) Wet / 158°F (70°C) Oil

Food Grade:
-22°F (-30°C) to 221°F (105°C) Dry /140°F (60°C) Wet / 158°F (70°C) Oil

Liquidtight fittings are intended for use in an environment where they could be exposed to machine coolant and/or shop oils. These fittings are subjected to an oil spray test when they are listed by UL.

Gibson Stainless offers rigid (heavywall) conduit. Proper wiring methods cited by NEC Article 501.10(A) permit all threaded rigid metal conduit (RMC) for use in hazardous locations. NEC Section 500.8(E) requires installing RMC with five threads fully engaged and wrench tight allowing gases within the raceway to cool before discharging into the atmosphere. RMC must meet the wrench-tight requirement for all locations, including hazardous. This wiring method also prevents arcing or sparking at threaded joints if a fault current passes over the conduit during a ground-fault event. Although full explosion prevention is not possible, the threaded connection confines any explosion to the inside of the conduit, thereby mitigating the possibility of an explosion in the larger area.

NFPA, UL, and OSHA agree on the importance of installing only approved wiring methods for all locations to ensure the electrical continuity of raceways. RMC is known for its ease of installation, durability, and is NEC-approved for all locations, including hazardous.